| Model / PN |
ORVALDI V1000 sinus 2U LCD / VOT(L)1000 |
ORVALDI V2000 (L) sinus 2U LCD / VOT(L)2000 |
ORVALDI V3000 (L) sinus 2U LCD / VOT(L)3000 |
| Capacity |
1000 VA / 800 W |
2000 VA / 1600 W |
3000 VA / 2400 W |
| INPUT |
| Voltage |
110/120 VAC or 208/220/230/240 VAC |
| Acceptable Voltage Range |
81-145 VAC or 162-290 VAC |
| Frequency Range |
60/50 Hz (auto sensing) |
| OUTPUT |
| Voltage Regulation (AC Mode) |
110/120 VAC or 208/220/230/240 VAC |
| Voltage Regulation (Batt. Mode) |
± 3 % (before battery alarm) |
| Frequency Range (Batt. Mode) |
50 Hz or 60 Hz ± 1 Hz |
| Current Crest Ratio |
3:1 |
| Harmonic Distortion |
8% max @ 100% linear load, 15% max @ 100% non-linear load (before alarm) |
| Waveform (Batt. Mode) |
Pure Sinewave |
| Transfer Time |
Typical 2-6 ms, 10ms max |
| EFFICIENCY |
| AC Mode |
97% |
97% |
| Buck & Boost Mode |
90% |
90% |
| Battery Mode |
85% |
87% |
| BATTERY |
| Standard Model |
| Type & Numbers |
|
12 V/9 Ah x 2 |
12 V/7 Ah x4 |
12 V/9 Ah x4 |
|
12 V/9 Ah x6 |
| Charging Voltage |
27.4 VDC ± 1% |
54.8 VDC ± 1% |
82.1 VDC ± 1% |
| Typical Recharge Time |
4 hours recover to 90% capacity |
|
| Long-run Model |
| Charging Current (max.) |
|
4 A / 8 A |
N/A |
4 A / 8 A |
|
4 A / 8 A |
| Charging Voltage |
|
27.4 VDC ± 1% |
N/A |
54.8 VDC ± 1% |
|
82.1 VDC ± 1% |
|
| PROTECTION |
| Full Protection |
Overload, discharge, and overcharge protection |
| INDICATORS |
| LCD Display |
AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Low Battery |
| ALARM |
| Battery Mode |
Sounding every 10 seconds |
| Low Battery |
Sounding every second |
| Overload |
Sounding every 0.5 second |
| Fault |
Continuously sounding |
| PHYSICAL |
| Standard Model |
| Dimension, D x W x H (mm) |
380 x 438 x 88 |
480 x 438 x 88 |
600 x 438 x 88 |
| Net Weight (kgs) |
|
14.23 |
21.08 |
23.1 |
|
32.24 |
|
| Long-run Model |
| Dimension, D x W x H (mm) |
|
380 x 438 x 88 |
N/A |
480 x 438 x 88 |
|
600 x 438 x 88 |
| Net Weight (kgs) |
|
10.8 |
N/A |
14 |
|
18 |
|
| ENVIRONMENT |
| Humidity |
0-90 % RH @ 0- 40°C (non-condensing) |
| Noise Level |
Less than 45dB |
| MANAGEMENT |
| Optional SNMP |
Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC |
| Smart RS-232/USB |
Power management from SNMP manager and web browser |